    • FN12 Series Indoor Load Break Switch

    FN12 Series Indoor Load Break Switch

    The switch disconnectors series FN12 are increasingly adopted in MV installations, owing to their superior interrupting features and to their capability to withstand the short-circuit currents which occur mainly as consequences of faults in distribution networks. The versions combined with HRC fuses are particularly suitable for the protection of distribution transformers up to 1250 kVA The use of FN12, designed for installation in compartmented switchboards have the following advantages: -Full segregation between the busbar compartment and the cable compartment, with switch disconnector in both "closed" and "open" position. -The moving contact, of the sliding vertical type, can be easily checked and cleaned with live bus-bars and earthing switch (ES) closed. -No adjustment is needed in the tripping mechanism of the switch fuse combination and of the ES: they are built together in a single unit, which is adjusted and checked during assembly in the factory, before the final test.

    Technical Information

    Technical Specification

     

     

     

     

    Rated voltage

    kV

    12

    24

    36

    Rated current

    A

    630

    630

    630

    Rated power frequency

    Hz

    50/60

    50/60

    50/60

    Short circuit making capacity

    kA Peak.

    67

    50

    50

    Peak withstand current

    kA Peak.

    82

    82

    66

    Short time current

    kA eff.

     

     

     

    1Sec.

     

    31.5

    31.5

     

    2Sec.

     

    25

    25

    25

    3Sec.

     

    20

    16

     

    Max. breaking capacity in co-operation with fuses IEC 62271-105(IEC 420 1990-11)

    A

    1600

    900

    300

    Max. fuse current(XRNT Fuse)

    A

    125

    80

    40

    Power frequency withstand voltage 50Hz 1 min,:

     

     

     

     

    - To earth and between poles

    kV

    42

    55

    95

    - Across isolating distance

    kV

    45

    70

    120

    Impulse withstand voltage 1.2/50μ s:

     

     

     

     

    - To earth and between poles

    kV

    75

    125

    190

    - Across isolating distance

    kV

    85

    145

    220

    Mechanism Endurance

    cycles

    2000

    2000

    2000


    Overall and installation dimensions