Hello! welcomeZhejiang Xikai Electric Co. , Ltd.
Zhejiang Xikai Electric Co. , Ltd.
Contact
Zhejiang Xikai Electric Co. , Ltd.
Mailbox:wzxikai@wzxikai.com
Tel:+86 577 61666 016
address:No.271, Weishiqi Road, Yueqing Economic Development Insuatrial Zone, Yueqing, Zhejiang.

product list

Indoor high voltage load switch
14/5000 Indoor vacuum circuit breaker
Outdoor vacuum circuit breaker
Outdoor high voltage load switch
Outdoor high voltage disconnector
Outdoor drop fuse
High voltage current limiting fuse series
High voltage complete set
current position:Home>Product Center

Product Center

    • FZN21 Series Indoor Vacuum Load Break Switch

    FZN21 Series Indoor Vacuum Load Break Switch

    FZN21 series indoor M.V. Vacuum load break switch and its fuse combination are applied for 12kV, 24kV and 40.5kV, 50/60Hz power systems. It widely use for industrial and mining area, to cooperate for Ring Main Units and Terminals. It can distribute, control and protect the electric power. This product fulfill with the requirements of following standards:IEC 60265-1/FDIS,IEC 60420 , GB16926 , GB3804 . This model of switch was combined with frame, isolator, Vacuum interrupter, earth switch, spring mechanism. It has good breaking capacity, safety, and long electrical endurance. This model can break on load current, over load current, and after cooperate with XRNT fuse, that can break short circuit current and protect the equipment work under loss phase. There are visible fracture. There is interlock between isolator, V-LBS and ES, which can forbidden mis-operation.

    Technical Information

    Technical Specification

     

     

     

     

    Rated voltage

    kV

    12

    24

    40.5

    Rated current

    A

    630

    630

    630

    Rated power frequency

    Hz

    50/60

    50/60

    50/60

    Short circuit making capacity

    kA Peak.

    50

    31.5

    31.5

    Peak withstand current

    kA Peak.

    50

    50

    50

    Short time current

    kA eff.

     

     

     

    1Sec.

     

    25

     

     

    3Sec.

     

    20

    20

    20

    Max. breaking capacity in co-operation with fuses IEC 62271-105(IEC 420 1990-11)

    A

    2000

    2000

    1700

    Max. fuse current(XRNT Fuse)

    A

    200

    200

    100

    Power frequency withstand voltage 50Hz 1 min,:

     

     

     

     

    - To earth and between poles

    kV

    42

    65

    95

    - Across isolating distance

    kV

    48

    79

    110

    Impulse withstand voltage 1.2/50μ s:

     

     

     

     

    - To earth and between poles

    kV

    75

    125

    185

    - Across isolating distance

    kV

    85

    145

    215

    Mechanism Endurance

     

     

     

     

    -Vauum interrupter

    cycles

    10000

    10000

    10000

    -Main switch and Earth Switch

    cycles

    2000

    2000

    2000


    Overall and installation dimensions