    • FZN25-12 Indoor Medium Voltage Vacuum Load Break Switch

    FZN25-12 Indoor Medium Voltage Vacuum Load Break Switch

    FZN25-12D/T630-20 Indoor AC medium voltage vacuum load break switch is three-phase AC 50/60 Hz, rated voltage 12kV indoor installation, which is suitable for using in industrial and mining situation and so on enterprise substation and transformer and cable charging current. It had manual and motor operating mechanism that is advantageous to realize remote control. FZRN25-12D/T[]-31.5 indoor AC medium voltage vacuum load break switch with fuse combination, The versions combined with HRC fuses are particularly suitable for the protection of distribution transformers up to 1250 kVA, to break fault current and over load current.


     Technical Information

    Technical Specification

     

     

    Rated voltage

    kV

    12

    Rated current

    A

    630

    Rated power frequency

    Hz

    50/60

    Short circuit making capacity

    kA Peak.

    50

    Peak withstand current

    kA Peak.

    50

    Short time current

    kA eff.

     

    1Sec.

     

    25

    3Sec.

     

    20

    Max. breaking capacity in co-operation with fuses IEC 62271-105(IEC 420 1990-11)

    A

    2000

    Max. fuse current(XRNT Fuse)

    A

    200

    Power frequency withstand voltage 50Hz 1 min,:

     

     

    - To earth and between poles

    kV

    42

    - Across isolating distance

    kV

    48

    Impulse withstand voltage 1.2/50μ s:

     

     

    - To earth and between poles

    kV

    75

    - Across isolating distance

    kV

    85

    Mechanism Endurance

     

     

    -Vauum interrupter

    cycles

    10000

    -Main switch and Earth Switch

    cycles

    2000


    Overall and installation dimensions