ZW7-40.5 outdoor high voltage vacuum circuit breaker is used for AC three-phase power system with 50Hz and voltage of 40.5kV, which is used for breaking, closing load current, overload current and short circuit current.
Technical Information
Technical Specification |
|
|
| ||||
Rated voltage |
|
|
| 40.5 | |||
Rated insulation
|
| Power frequency withstand voltage
| Dry | kV | 95 | ||
| Wet |
| 80 | ||||
level |
|
| Lightning impulse withstand voltage (peak) |
| 185 | ||
Rated current |
|
| A | 1250、1600、2000 | |||
Rated short-circuit breaking current |
| kA | 20、25、31.5 | ||||
Rated operation sequence |
|
| Points -0.3s combined -180s combined | ||||
Rated short circuit current breaking times | Times | ≥30 | |||||
Rated short circuit closing current (peak) | kA | 50、63、80 | |||||
Rated peak withstand current |
|
|
| ||||
Rated short-time withstand current |
| kA | 20、25、31.5 | ||||
Rated short circuit continuous current |
| S | 4 | ||||
Average opening speed |
| m/s | 1.5±0.2 | ||||
Average closing speed |
|
| 0.7±0.2 | ||||
Contact closing bounce time |
|
| ≤2 | ||||
Three-phase combined (minute) gate synchronous time difference | S | ≤2 | |||||
Closing time |
|
|
| ≤150 | |||
Opening time |
|
|
| ≤60 | |||
Mechanical life |
|
| Times | 10000 | |||
Rated operating voltage and auxiliary circuit rated voltage |
| V
| DC220、110、24 | ||||
AC220、110、24 | |||||||
DC resistance per phase circuit (without transformer) | μΩ | ≤100 | |||||
Dynamic and static contacts allow wear thickness | mm | 3 | |||||
Weight |
|
| kg | 800 |