LW38-40.5 outdoor AC high voltage sulphur hexafluoride circuit breaker (hereinafter referred to as "circuit breaker") is an outdoor high-voltage power distribution switchgear with three-phase AC 50Hz and rated voltage of 40.5kV. It can be used to divide and match rated current and fault current, cast and cut capacitor group and conversion line. It is especially suitable for frequent operation or as a contact breaker. The circuit breaker uses SF6 gas as the arc extinguishing and insulating medium, and is installed outdoors. It adopts an elevated porcelain column structure. The circuit breaker complies with GB 1984-201 4 “High Voltage AC Circuit Breaker”, DL/T 402-2016 “High Voltage AC Circuit Breaker” and JB/T 9694-2008 “High Voltage AC Sulfur Hexafluoride Circuit Breaker” and other technical standards.
Environmental Conditions
1、 Altitude: no more than 1000m, if the altitude is higher than 1000m, the rated insulation level should be corrected accordingly;2、 Ambient temperature: upper limit +45℃ , lower limit -40℃ , maximum daily temperature difference of 25K;
3、 Humidity: average daily relative humidity ≤ 95%, average monthly relative humidity ≤90%;
4、Solar radiation intensity: ≥0.1W/cm2;
5、Wind speed: 34m / s;
6、Wind pressure: 700Pa;
7、Pollution level: e level;
8、Ice thickness: ≤10mm;
9、 Tolerance to earthquake: horizontal acceleration 0.3g, vertical acceleration 0.2g
Main Features
1、 Using SF6 gas to extinguish arc and insulation, excellent insulation performance;2、The structure is simple, and the maintenance period is long;
3、Strong breaking ability and long mechanical life;
4、 Either built-in or external current transformer, high measurement accuracy;
5、 Built-in intelligent wet temperature controller to ensure safe and reliable operation of circuit breakers in high and cold regions;
6、 The overall sealing design of the housing has been improved to effectively prevent the bad weather caused by sandstorms and other bad weather.
Technical Information
Technical Specification |
|
|
| |
Rated frequency |
| Hz | 50 | |
Rated voltage |
| kV | 40.5 | |
Rated current |
| A | 1250、1600、2000 | |
Rated short-circuit breaking current | kA | 31.5 | ||
Rated short circuit closing current | kA | 80 | ||
Rated short-time withstand current | kA | 31.5 | ||
Rated peak withstand current |
| kA | 80 | |
Rated out-of-step breaking current | kA | 10 | ||
Rated short circuit duration |
| S | 4 | |
Rated short-circuit breaking current breaking times | Times | 1 0 | ||
Rated short-time power frequency withstand voltage
|
| Interphase and ground (dry test) | kV/min | 95/1 |
| Fracture (dry test) | kV/min | 118/1 | |
| Phase to ground (wet test) | kV/min | 80/1 | |
| Auxiliary circuit to ground | kV/min | 2/1 | |
Rated lightning impulse withstand voltage |
| Phase to ground | kV | 185 |
| Fracture | kV | 215 | |
Rated operating voltage and auxiliary circuit rated voltage | V | AC220、DC220 | ||
Main loop resistance |
| Rated current 1600A and below | μΩ | ≤90 |
|
| 1600A Rated current greater than 1600A | ms | ≤40 |
Closing time |
| Under AC voltage | ms | ≤100 |
|
| Under DC voltage | ms | 55~100 |
Opening time |
| Under AC voltage | ms | ≤60 |
|
| Under DC voltage | ms | 30~65 |
|
| Continued on the table | |
Technical Specification |
|
|
|
Combined-minute time |
| ms | ≥120(Operating state) ≥120 |
Split-time |
| ms | ≤50 |
Full break time |
| ms | ≤78 |
Rated operation sequence |
| ms | O-0.3S-CO-180s-CO |
Moving contact stroke |
| mm | 96±2.5 |
Contact opening distance |
| mm | 60±1.5 |
Closing buffer stroke |
| mm | 10±2 |
Phase-to-phase closure |
| ms | ≤3 |
Phase-to-phase closure |
| ms | ≤3 |
Phase spacing |
| mm | 725 |
SF6 annual air leak rate |
| % | ≤0.5 |
SF6 gas moisture content (ppm, gauge pressure at 20 ℃) | Handover acceptance value | V/V | ≤150 |
Running value | V/V | ≤300 | |
SF6 gas rated pressure (20 ° C gauge pressure) | Mpa | 0.45 | |
SF6 gas supplemental pressure (gauge pressure at 20 °C) | Mpa | 0.42 | |
SF6 gas blocking pressure (gauge pressure at 20 ° C) | Mpa | 0.4 | |
Mechanical life |
| Times | 6000 |
SF6 gas weight |
| kg | 5 |
Weight | With CT | kg | 800 |
| Without CT | kg | 1000 |
Download Google
1、Please indicate the product name and model number;2、Please indicate the rated voltage, rated current and rated short-circuit breaking current;
3、Please indicate the operating voltage of the operating mechanism and the auxiliary (control) circuit;
4、Please indicate the number of current transformers, installation methods (built-in or external), ratio, accuracy and rated capacity;
5、Please specify other special requirements, such as the type of cold, mounting brackets and the number of auxiliary contacts;
6、Please indicate the order quantity and delivery time