Hello! welcomeZhejiang Xikai Electric Co. , Ltd.
Zhejiang Xikai Electric Co. , Ltd.
Contact
Zhejiang Xikai Electric Co. , Ltd.
Mailbox:wzxikai@wzxikai.com
Tel:+86 577 61666 016
address:No.271, Weishiqi Road, Yueqing Economic Development Insuatrial Zone, Yueqing, Zhejiang.

product list

Indoor high voltage load switch
14/5000 Indoor vacuum circuit breaker
Outdoor vacuum circuit breaker
Outdoor high voltage load switch
Outdoor high voltage disconnector
Outdoor drop fuse
High voltage current limiting fuse series
High voltage complete set
current position:Home>Product Center

Product Center

    • FZW32 outdoor high voltage isolation vacuum load switch

    FZW32 outdoor high voltage isolation vacuum load switch

    FZW32 Outdoor Vacuum Load Break Switch is used for power system, it is suitable for 12kV 50Hz three-phase power system. The frame of this switch is applied with the stainless steel or steel with hot-dip galvanization and anti-UV coating. All the elements are used the stainless steel. To make sure the stable and perfect function of the switch.

    Technical Information

    Technical Specification

     

     

     

     

    Rated voltage

     

    kV

    12

    40.5

    Rated frequency

     

    Hz

    50

    50

    Rated current

     

    A

    630

    1250

    Rated active load breaking current

    A

    630

    1250

    Rated closed-loop breaking current

    A

    630

    1250

    5% rated active load breaking current

    A

    31.5

    62.5

    Rated cable charging breaking current

    A

    10

    25

    Rated no-load transformer breaking capacity

    kVA

    1600

    1600

    Rated breaking capacitor bank current

    A

    100

    100

    1min power frequency withstand voltage: vacuum fracture, phase, relative / isolation fracture

    kV

    42/48

    68/95/110

    Lightning impulse withstand voltage: phase-to-phase, relative/isolated fracture

    kV

    75/85

    185/215

    ated short-time withstand current (thermal stability)

    kA

    20

    25

    Rated short circuit duration

    S

    4

    4

    ated peak withstand current (dynamic stability)

    kA

    50

    63

    Rated short circuit closing current

    kA

    50

    63

    Mechanical life

     

    Times

    10000

    10000

    Vacuum arcing contacts allow wear thickness

    mm

    0.5

    0.6

    Manual operating torque

     

    N.m

    ≤200

    ≤300

     

     

    Contact opening distance

    mm

     

    5±1

     

     

    Average opening speed

    m/s

     

    1.1±0.2

     

     

    Three-phase opening

    ms

     

    ≤5

    Load switch vacuum interrupter assembly adjustment

     

    Three-phase closing

    ms

     

    ≤2

     

     

    Charged body and relative distance

    mm

     

    >200

     

     

    Auxiliary loop resistance

    μΩ

     

    ≤300


    Overall and installation dimensions