FZW32 Outdoor Vacuum Load Break Switch is used for power system, it is suitable for 12kV 50Hz three-phase power system. The frame of this switch is applied with the stainless steel or steel with hot-dip galvanization and anti-UV coating. All the elements are used the stainless steel. To make sure the stable and perfect function of the switch.
Technical Information
Technical Specification |
|
|
|
| |
Rated voltage |
| kV | 12 | 40.5 | |
Rated frequency |
| Hz | 50 | 50 | |
Rated current |
| A | 630 | 1250 | |
Rated active load breaking current | A | 630 | 1250 | ||
Rated closed-loop breaking current | A | 630 | 1250 | ||
5% rated active load breaking current | A | 31.5 | 62.5 | ||
Rated cable charging breaking current | A | 10 | 25 | ||
Rated no-load transformer breaking capacity | kVA | 1600 | 1600 | ||
Rated breaking capacitor bank current | A | 100 | 100 | ||
1min power frequency withstand voltage: vacuum fracture, phase, relative / isolation fracture | kV | 42/48 | 68/95/110 | ||
Lightning impulse withstand voltage: phase-to-phase, relative/isolated fracture | kV | 75/85 | 185/215 | ||
ated short-time withstand current (thermal stability) | kA | 20 | 25 | ||
Rated short circuit duration | S | 4 | 4 | ||
ated peak withstand current (dynamic stability) | kA | 50 | 63 | ||
Rated short circuit closing current | kA | 50 | 63 | ||
Mechanical life |
| Times | 10000 | 10000 | |
Vacuum arcing contacts allow wear thickness | mm | 0.5 | 0.6 | ||
Manual operating torque |
| N.m | ≤200 | ≤300 | |
| Contact opening distance | mm |
| 5±1 | |
| Average opening speed | m/s |
| 1.1±0.2 | |
| Three-phase opening | ms |
| ≤5 | |
Load switch vacuum interrupter assembly adjustment | Three-phase closing | ms |
| ≤2 | |
| Charged body and relative distance | mm |
| >200 | |
| Auxiliary loop resistance | μΩ |
| ≤300 |
Overall and installation dimensions