    • GW1-12 Outdoor High Voltage Ac Disconnector

    GW1-12 Outdoor High Voltage Ac Disconnector

    GW1-12 series outdoor high-voltage AC isolating switch (hereinafter referred to as “isolation switch”), suitable for installation on outdoor high-voltage power distribution equipment line, for 10kV line to be connected under voltage and no load, and for high voltage to be overhauled Electrical equipment such as busbars and circuit breakers can be electrically isolated from live high-voltage lines, and can also be used to separate small capacitive currents and inductor currents. The isolating switch is a double-column vertical open type with manual or electric mechanism for three-phase linkage. The isolating switch complies with GB 1985-2014 "High Voltage AC Isolation Switch and Grounding Switch", DL/T 486-2010 "High Voltage AC Isolation Switch and Grounding Switch" and other technical standards.

    Technical Information

    Technical Specification

     

     

     

     

     

     

     

     

     

     

     

    Rated voltage

     

    kV

     

     

     

    12

     

     

    24

    40.5

    Rated frequency

     

    Hz

     

     

     

     

     

    50

     

     

    Rated current

     

    A

     

    630

     

    1250(1600)

    630

    Rated short-time withstand current and duration

    Isolation switch

    kA/s

    20/4

     

    25/4

     

    25/4

     

    31.5/4

    20/4

    25/4

    Grounding switch

    kA/s

    20/2

     

    25/2

     

    25/2

     

    31.5/2

    20/2

    25/2

    Rated peak withstand current

    kA

    25

     

    63

     

    63

     

    80

    25

    63

    Rated short-time power frequency withstand voltage

    Interphase and ground (dry test)

    kV/min

     

     

     

    42/1

     

     

    50

    95

    Fracture (dry test)

    kV/min

     

     

     

    48/1

     

     

    60

    115

    Phase to ground (wet test)

    kV/min

     

     

     

    42/1

     

     

    50

    85

    Lightning impulse withstand voltage

    Phase to ground

    kV

     

     

     

    75

     

     

    125

    185

    Fracture

    kV

     

     

     

    85

     

     

    145

    215

    Loop resistance

     

    μΩ

    ≤100

     

    ≤80

    ≤90

    ≤100

         

     

    Mechanical life  
    Times
    Isolation switch / grounding switch 