Hello! welcomeZhejiang Xikai Electric Co. , Ltd.
Zhejiang Xikai Electric Co. , Ltd.
Contact
Zhejiang Xikai Electric Co. , Ltd.
Mailbox:wzxikai@wzxikai.com
Tel:+86 577 61666 016
address:No.271, Weishiqi Road, Yueqing Economic Development Insuatrial Zone, Yueqing, Zhejiang.

product list

Indoor high voltage load switch
14/5000 Indoor vacuum circuit breaker
Outdoor vacuum circuit breaker
Outdoor high voltage load switch
Outdoor high voltage disconnector
Outdoor drop fuse
High voltage current limiting fuse series
High voltage complete set
current position:Home>Product Center

Product Center

    • GW5-40.5W Outdoor High Voltage Ac Disconnector

    GW5-40.5W Outdoor High Voltage Ac Disconnector

    GW5-40.5 series outdoor high-voltage AC isolating switch (hereinafter referred to as “isolation switch”) is an outdoor high-voltage electrical equipment with a frequency of 50Hz. It is used for the connection of high-voltage lines under voltage and no load, and for the high-voltage busbars being repaired. Electrical equipment such as circuit breakers can be electrically isolated from live high-voltage lines. It can also be used to separate small capacitive currents and inductor currents. The isolating switch complies with GB 1985-2014 "High Voltage AC Isolation Switch and Grounding Switch", DL/T 486-2010 "High Voltage AC Isolation Switch and Grounding Switch" and other technical standards

    Technical Information

    Technical Specification

     

     

     

     

     

     

     

    Rated voltage

    kV

     

    40.5

     

     

    Rated frequency

    H

     

    50

     

     

    Rated current

    A

    630

     

    1250

     

    2000

    Rated short-time withstand current

    kA

    20/25

     

    25/31.5

     

    31.5

    Rated short-time withstand current (peak)

    kA

    50/63

     

    63/80

     

    80

    Rated short-time power frequency withstand voltage

    kV/min

    95/1nterphase, earth, dry test

    118/1nterphase, earth, dry test

    95/1nterphase, ground, and wet test

    Rated lightning impulse withstand voltage

    kV

    185/1 earth

    215 Fracture

    Rated short-time withstand current duration

    S

    4 Isolation switch、

    2Grounding switch

    Creepage distance

    mm

    ≥1256Class e antifouling

     

    Main loop resistance

    μΩ

    ≤100

     

     

     

    ≤80

     

    Operating mechanism

    Human operating agency

     

    CS17-G5 Without grounding switch

     

    Main knife Cs17-G5, ground knife Cs17-G2 (with single/double earthing switch)

    Motor operating mechanism

     

    CJ6 type, motor voltage AC380V or DC220V, control voltageAC220V or DC220V, auxiliary contact 8 normally open 8 nor mally closed (standard)

    Mechanical life

    Times

     

    Isolation switch grounding switch


    Overall and installation dimensions