Hello! welcomeZhejiang Xikai Electric Co. , Ltd.
Zhejiang Xikai Electric Co. , Ltd.
Contact
Zhejiang Xikai Electric Co. , Ltd.
Mailbox:wzxikai@wzxikai.com
Tel:+86 577 61666 016
address:No.271, Weishiqi Road, Yueqing Economic Development Insuatrial Zone, Yueqing, Zhejiang.

product list

Indoor high voltage load switch
14/5000 Indoor vacuum circuit breaker
Outdoor vacuum circuit breaker
Outdoor high voltage load switch
Outdoor high voltage disconnector
Outdoor drop fuse
High voltage current limiting fuse series
High voltage complete set
current position:Home>Product Center

Product Center

    • FLN36 Indoor AC SF6 Load Break Switch

    FLN36 Indoor AC SF6 Load Break Switch

    FL(R)N36 Indoor AC High Voltage SF6 Load Break Switch and LBS-Fuse Combination are used for the three-phase AC 50/60Hz RMU and terminal power station. The switches are suitable for protecting the 10kV, 24kV and 35kV power system's on load situation. The switch can switch off the on load current, closed loop current, no load transformer capacity and cable charging current. The switch with fuse combination can cut off any current, when the current is in the range of the rated short-circuit breaking current. They are suitable for the RMU, combined transformer, etc..

    Technical Information

    Technical Specification

     

     

     

     

    Rated voltage

    kV

    12

    24

    40.5

    Rated current

    A

    630

    630

    630

    Rated power frequency

    Hz

    50/60

    50/60

    50/60

    Short circuit making capacity

    kA Peak.

    62.5

    50

    50

    Peak withstand current

    kA Peak.

    62.5

    50

    50

    Short time current

    kA eff.

     

     

     

    1Sec.

     

    25

     

     

    2Sec.

     

     

    20

    20

    Max. breaking capacity in co-operation with fuses IEC 62271-105 (IEC 420 1990-11)

    A

    1530

    920

    630

    Mainly active load breaking capacity

    A

    630

    630

    630

    Cable charging current

    A

    630

    630

    630

    Power frequency withstand voltage 50Hz 1 min,:

     

     

     

     

    - To earth and between poles

    kV

    42

    55

    95

    - Across isolating distance

    kV

    45

    70

    120

    Impulse withstand voltage 1.2/50μ s:

     

     

     

     

    - To earth and between poles

    kV

    75

    125

    190

    - Across isolating distance

    kV

    85

    145

    220

    Mechanism Endurance

    cycles

    1000

    1000

    1000


    Overall and installation dimensions